H2CON-6 is especially suited for H2 gas level detection, ventilation control and alarm applications.
-
It is a remote Hydrogen area monitoring device.
-
It is applied to Hydrogen storage and handling areas where there is danger of Hydrogen accumulation resulting in explosive atmosphere.
-
Its micro-controller scans each of the six sensors with a fixed alarm threshold of 1%, 2% and >2.5% and gives control/alarm outputs of up to three relays.
-
It also has LED front panel indicators.
-
These outputs can then be used for ventilation fan control, hooter or overriding shut-down of charging etc. for the system to take early safety measures.
-
Front panel LED bar graph indications for each channel is provided. Thus exact location of fault can be identified.
-
An optional feature of H2CON-6 is that it can be connected over an isolated RS485 bus with MODBUS protocol.
SPECIFICATIONS OF MULTICHANNEL HYDROGEN ALARM MONITOR: H2CON-6
|
1
|
H2 Sensor compatibility
|
H2SENSE-1205 and CHS-HTR-PH-100-5V-CM
|
2
|
Range
|
0 to 2% Hydrogen (0 to 4 % optional)
|
3
|
No. of Channels
|
Up to 6 Nos.
|
4
|
Max distance
|
From sensors to alarm module - 20M. Can be customized for distances greater than 20M
|
5
|
Sensor Termination
|
PCB Screw terminations
|
6
|
Action time
|
1 second for common alarm outputs
|
7
|
Outputs
|
Relay 1: “HI” Fan Control
Relay 2: “XHi” Charging shut down & Hooter
Relay 3: “XXHi” Additional actions ( provided only on customer demand)
|
8
|
Communication
|
RS485 (Galvanic isolation ) with Modbus protocol (Optional against order)
|
9
|
Output Terminations
|
NO/NC contacts 5 Amp/250V AC non inductive load
|
10
|
Power
|
11V to 14.5V DC from Battery,
20V to 30V DC optional, 24V AC optional ( Customer to specify )
|
11
|
Power to Transducers
|
Resistive and active current limit to 100mA max
|
12
|
Housing
|
IP65, 150X80X55 ABS Plastic and Wall Mounting
|
Specification subject to changes without prior notice, due to continuous R&D and development of Company’s Products |